1st Player NGDP 1300W PSU Review

Protection Features

OCP (Cold @ 29°C) 12V: 138.4A (128.15%), 12.179V
5V: >30.4A (>152%), <4.947V
3.3V: >30.3A (>151.5%), <3.322V
5VSB: 4.1A (136.67%), 4.823V
OCP (Hot @ 43°C) 12V: 134.6A (124.63%), 12.179V
5V: >30.4A (>152%), <4.944V
3.3V: >30.5A (>152.5%), <3.323V
5VSB: 4.1A (136.67%), 4.82V
OPP (Cold @ 30°C) 1771.11W (136.24%)
OPP (Hot @ 41°C) 1707.11W (131.32%)
OTP ✓ (131°C @ 12V Heat Sink)
SCP 12V to Earth: ✓
5V to Earth: ✓
3.3V to Earth: ✓
5VSB to Earth: ✓
-12V to Earth: ✓
PWR_OK Proper operation
NLO
Fan Failure Protection
SIP Surge: MOV
Inrush: NTC Thermistor & Bypass relay

OCP is correctly set at 12V, and the same goes for OPP. On the other hand, OCP needs adjustment on the minor rails. This was also an issue with the 1000W unit. There is no need for >30A on the minor rails, especially at 3.3V.